Overview
The 07 KT 98 basic unit operates as a versatile component in decentralized automation systems. It can function as a bus master or slave in the Advant Controller 31, or as a standalone unit. It requires a power supply of 24 V DC.
Main Features
- Digital Inputs:
- 24 digital inputs with LED displays.
- Digital Outputs:
- 16 digital transistor outputs with LED displays.
- 8 digital inputs/outputs with LED displays.
- Analog Inputs:
- 8 individually configurable analog inputs:
- Voltage: 0…10 V, 0…5 V, ±10 V, ±5 V.
- Current: 0…20 mA, 4…20 mA.
- Differential inputs and Pt100 (2-wire or 3-wire).
- Configurable as digital inputs.
- 8 individually configurable analog inputs:
- Analog Outputs:
- 4 individually configurable analog outputs: ±10 V, 0…20 mA, 4…20 mA.
- Counters:
- 2 counters for frequencies up to 50 kHz, configurable in 7 operating modes.
- Communication Interfaces:
- 1 CS31 system bus interface for expansion.
- 1 interface for connecting communication modules (e.g., 07 KP 90).
- 2 serial interfaces (COM1, COM2):
- MODBUS interfaces.
- Programming and test functions.
- Freely programmable interfaces.
- Real-Time Clock:
- Integrated real-time clock for timekeeping.
- Diagnostics:
- LEDs for operating conditions and error messages.
- Extensive diagnosis functions including self-diagnosis and system bus diagnosis.
- User Convenience:
- Detachable screw-type terminal blocks.
- Fastening options: screws or DIN rail.
- RUN/STOP switch for program execution control.
- Data Storage:
- Integrated Flash EPROM for storing programs and data.
- Exchangeable SmartMedia Card (07 MC 90) for user data and operating system updates.
- Lithium battery (07 LE 90) for backing up RAM data and real-time clock.
Project Planning / Start-Up
- Programming:
- Use AC31 programming software on IBM-compatible PCs (refer to documentation 907 AC 1131).
- Online Modifications:
- Modify user programs without interrupting operation.
- Operating Modes:
- Stand-alone basic unit.
- Bus master basic unit.
- Slave basic unit.
- Data Backup:
- Save data during power cycles using the integrated battery or Flash EPROM.
- PROFIBUS DP Interface:
- Project planning aligns with procedures for 07 KT 97. See the “System Description” for details.
About Us
✨ With 13 years of global supply experience, we bring you exceptional service.
🌍 We directly source authentic licensed products from abroad, ensuring competitive prices, reliable after-sale warranties, and an extensive selection of models backed by ample inventory.
💥 Contact us for orders of more than 1 product, and we’ll be delighted to offer you a discount.
🤔 Have questions or special requests? Feel free to get in touch with us.
💰 If you find the same parts at a lower price from other suppliers, we’ll match or beat that price.
🛠️ Need spare parts? Let us know, and we’ll gladly assist you further. Your inquiry is eagerly awaited.
📧 Contact Us
- E-mail: [email protected]
🕒 Business Hours: 24/7
🏢 Address: No.601, Hongwen Liuli, Siming District, Xiamen, China
Recommended Products
Manufacturer | Model | Link |
---|---|---|
ABB | 70BV05A-ES | link |
ABB | 70EA2a-ES | link |
ABB | 70EA01B-ES | link |
ABB | 70EB0lb-E | link |
ABB | 70AB01C-ES | link |
ABB | 70BK03c-E | link |
ABB | 70PR05b-ES | link |
ABB | 70E105a-E | link |
ABB | 70BT01C | link |
ABB | 70AA02B-E | link |
ABB | NKTT01-3 | link |
ABB | NWIO-01 | link |
ABB | UFC719AE01 3BHB003041R0101 | link |
ABB | 57619414 | link |
ABB | KUC711AE 3BHB004661R0101 | link |