3500/62 Process Variable Monitor

The 3500/62 Process Variable Monitor is a 6-channel device designed to continuously monitor critical parameters, such as pressures, flows, temperatures, and levels, to protect machinery. It accepts +4 to +20 mA current inputs or proportional voltage inputs between -10 Vdc and +10 Vdc. The monitor conditions the signals and compares them to user-programmable alarm setpoints.

Key Features:

  • Continuous Monitoring: Compares monitored parameters against alarm setpoints to trigger alarms for machinery protection.
  • Essential Information: Provides valuable machine data for both operations and maintenance personnel.
  • Flexible Inputs: Accepts current and voltage measurements, programmable via 3500 Rack Configuration Software.
  • Multiple Input Scenarios: Supports +/-10 Vdc, 4-20 mA (isolated), or 4-20 mA with intrinsically safe zener barriers.
  • Intrinsically Safe Power: The Internal Barrier I/O option provides external power to 4-20 mA transducers.
  • Triple Modular Redundant (TMR) Configuration: Ensures accuracy with two types of voting to avoid single-point failures, protecting machinery.

Specifications

Inputs:

  • Signal Types:
    • +/-10 Vdc I/O: Range from -10 Vdc to +10 Vdc
    • 4-20 mA Barrier I/O: Range of 4-20 mA DC
    • 4-20 mA Isolated I/O: Range of 4-20 mA DC
  • Voltage Compliance (4-20 mA Barrier I/O): 13.66 V
  • Isolation (4-20 mA Isolated I/O): 500 Volts
  • Input Impedance:
    • +/-10 V I/O: 1 MΩ
    • 4-20 mA Barrier I/O & Isolated I/O: 50 Ω
  • Power Consumption: 7.0 Watts (typical)
  • External Transducer Power (Internal Barrier I/O Only): +24 Vdc ± 5% @ 250 mA max. (Fused)

Outputs:

  • Front Panel LEDs:
    • OK LED: Indicates when the monitor is operating correctly.
    • TX/RX LED: Indicates communication with other modules in the 3500 rack.
    • Bypass LED: Shows when the monitor is in Bypass Mode.

Accuracy:

  • Within ±0.33% of full-scale (typical), ±1% maximum.

Full Scale Range:

  • Maximum: 20,000 units mapped over the input signal span.
  • Minimum Input Signal Span: 2 Volts for voltage input.

For more detailed specifications and information, please refer to the full datasheet: 3500/62 Process Variable Monitor Datasheet.